Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
BMXNOE0110 PV11 Firmware Compatibility Issue
Issue
This Resolution explains a firmware compatibility issue with the BMXNOE0110 at PV11.


Product Line
BMXNOE0110


Resolution
Component obsolescence required a replacement part for the BMXNOE0110's.  Modules with the new flash component are identified as PV11, which resulted in a new firmware version 5.9.
  • BMXNOE0110's at PV11 or higher are only compatible with firmware versions 5.9 or higher.
  • BMXNOE0110's at PV11 or higher cannot be downgraded with firmware versions lower than v5.9.
  • BMXNOE0110 firmware version 5.9 and higher are compatible with all BMXNOE0110 PV versions.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings