Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can the Altivar ATV312 drive be used as a phase converter?

Issue:
Can the ATV312 be used as a phase converter?

Product Line:
Altivar 312 for single phase line power

Environment:
VFD for single phase line power

Cause:
VFDs to be used as phase converters, to convert single phase line power to 3 phase line power.

Resolution:
Schneider offers the ATV312 that can be used to convert single phase line power to 3 phase output.  For selection: see the ATV312 quick start annex link below.
https://www.se.com/us/en/download/document/S1B16328/

Using a drive as a phase converter is possible only for motors. DO NOT USE DRIVES FOR PHASE CONVERTER FOR MACHINES.
The "input phase loss detection" must be deactivated (IPL=no)

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings