To check that a Vigilohm XM200 is operating correctly:
- Disconnect terminal 4 from the line supply (value indicated: 999).
- Connect terminal 4 to terminal 11. If R=0 then the Vigilohm is operating correctly.
- If R=999 remains displayed permanently, the Vigilohm XM200 is faulty.