Issue:
The actual value does not match the analog output of the drive.
Product Line:
Altivar Machines
Environment:
All models and serial numbers
Cause:
The most common cause is that the maximum frequency (tFr) is not set the same as the high speed (HSP) setting.
Resolution:
The analog output is based off of the maximum frequency setting. The default maximum frequency is set at 20% above the standard motor frequency (bFr). If the bFr is 60 the tFr is 72. Changing tFr will cause the analog output to match the actual value.
The actual value does not match the analog output of the drive.
Product Line:
Altivar Machines
Environment:
All models and serial numbers
Cause:
The most common cause is that the maximum frequency (tFr) is not set the same as the high speed (HSP) setting.
Resolution:
The analog output is based off of the maximum frequency setting. The default maximum frequency is set at 20% above the standard motor frequency (bFr). If the bFr is 60 the tFr is 72. Changing tFr will cause the analog output to match the actual value.
Released for: Schneider Electric UK