Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can I run an ATV312 in 3 wire control while in sink source mode?

Issue:
N/A

Product Line:
Altivar Machines, Altivar 312

Environment:
All serial numbers for ATV312

Cause:
N/A

Resolution:
No, sinking the logic inputs on an ATV312 will not work with 3 wire control. To use 3 wire control you would have to source the inputs

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings