For the PM710 how do you read the double word modbus registers?
this details the registers in the PM710 meter.
PM700 modbus register communications
Modbus register of PM700 starts from 1 other than 0. By changing Addressing convention settings, the customer will see the right data.

In my test, the data are consistent. The register address displayed in the Modbus master tool is 1 offset below the address they got from the PM700 modbus register doc. For example, Freq is in 41019.

PM700 modbus register communications
Modbus register of PM700 starts from 1 other than 0. By changing Addressing convention settings, the customer will see the right data.
In my test, the data are consistent. The register address displayed in the Modbus master tool is 1 offset below the address they got from the PM700 modbus register doc. For example, Freq is in 41019.
Released for: Schneider Electric UK