How to define the part number of Power pact 4 MCCB?
When selecting the part number for a MCCB to fit in to the Powerpact 4 Panelboards you must consider the following
- Current Rating
- Number of Poles ( For single pole or double pole you must know which phase will be used to feed these MCCB's - NOTE: if you order a 100A MCCB for L1 phase , it will only ever plug on to L1 busbar inside the board)
- Trip unit type (TMD , Micrologic 2/5/6)
- kA rating (Maximum fault current that the Circuit breaker can handle)
1P and 2P MCCB's Page 10 of the PDF attached - Fixed thermal and magnetic settings - non adjustable - ( 1Pole 25kA at 230v L-N , 2 Pole 85kA at 230v)
3P and 4P MCCB's Page 11 of the PDF attached
<250A MCCB's
up to 250A the MCCB's come with a Thermal Magnetic Trip unit refrenced TM100D for example - this is a 100A version
Thermal (Overload) is adjustable by 0.7 x in and Magnetic (Short Circuit) is fixed up to 160A , 200A and 250A TMD Trip units have adjustable magnetic protection up to 10 x in)
400/630A MCCB's
400/630A MCCB's come with a Micrologic 2.3 Trip unit as standard - This trip unit is an electronic trip unit so rather than the thermal and magnetic operation it uses electronics to trip the breaker
Overload is adjustable by 0.4 x in and Short circuit is Adjustable up to 10 x in)
In = nominal current rating of the MCCB
For other kA ratings and Trip unit variants see Page 12 of the PDF
Please see attached PDF showing the Powerpact 4 Section of our latest catalogue to select the reference you require
- Current Rating
- Number of Poles ( For single pole or double pole you must know which phase will be used to feed these MCCB's - NOTE: if you order a 100A MCCB for L1 phase , it will only ever plug on to L1 busbar inside the board)
- Trip unit type (TMD , Micrologic 2/5/6)
- kA rating (Maximum fault current that the Circuit breaker can handle)
1P and 2P MCCB's Page 10 of the PDF attached - Fixed thermal and magnetic settings - non adjustable - ( 1Pole 25kA at 230v L-N , 2 Pole 85kA at 230v)
3P and 4P MCCB's Page 11 of the PDF attached
<250A MCCB's
up to 250A the MCCB's come with a Thermal Magnetic Trip unit refrenced TM100D for example - this is a 100A version
Thermal (Overload) is adjustable by 0.7 x in and Magnetic (Short Circuit) is fixed up to 160A , 200A and 250A TMD Trip units have adjustable magnetic protection up to 10 x in)
400/630A MCCB's
400/630A MCCB's come with a Micrologic 2.3 Trip unit as standard - This trip unit is an electronic trip unit so rather than the thermal and magnetic operation it uses electronics to trip the breaker
Overload is adjustable by 0.4 x in and Short circuit is Adjustable up to 10 x in)
In = nominal current rating of the MCCB
For other kA ratings and Trip unit variants see Page 12 of the PDF
Please see attached PDF showing the Powerpact 4 Section of our latest catalogue to select the reference you require
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Category:
Explore more
Range:
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.