What is the usage of VPS (voltage power supply) module of Micrologic X in MTZ air circuit breakers?

Article available in these languages: Spanish

The Micrologic X’s internal voltage power supply module (VPS) is an optional module of Micrologic X control units. It allows to have power supply on the Micrologic X control unit (24VDC) even in the cases where there is not enough current going through the Masterpact MTZ air circuit breakers or if there is no external power supply. It allows to make operational, like some of the advanced functions inside Micrologic X, in particular the local HMI.

Three important things to remind:

1) Basic protection are independent of this VPS module.
2) During a trip event, this module is not able to provide power to the Micrologic X control unit (due to the fact that the power is coming downstream the circuit breaker).
3) This module is a compulsory option when Micrologic 7.0 X is required.

MTX Micrologic Control unit MTZ Micrologic contrl unit schematic

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings