Issue:
Altivar Process Drive power up with Safe Torque Off on the display
Product Line:
ATV
Environment:
All
Cause:
Wiring
Resolution:
The VFD safety feature requires 24Vdc input on STOA and STOB terminals. If there is no field wiring to these terminals, you must leave or install a jumper from 24v to STOA / STOB on top of the drive in the CN2 position.
Altivar Process Drive power up with Safe Torque Off on the display
Product Line:
ATV
Environment:
All
Cause:
Wiring
Resolution:
The VFD safety feature requires 24Vdc input on STOA and STOB terminals. If there is no field wiring to these terminals, you must leave or install a jumper from 24v to STOA / STOB on top of the drive in the CN2 position.
Released for:Schneider Electric UK

