Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
ATV6xx, ATV9xx when monitoring LCr (motor current) over communications, what feedback would you expect?

Article available in these languages: Spanish

Issue:
Expected feedback while monitoring LCr (motor current) over Communications.

Product Line:
ATV

Environment:
All

Cause:
Communication

Resolution:
LCR unit: [A]
drives up to     ..D15           coeff.: 0.01
drives:     D18..  to ..C16     coeff.: 0.1
drives higher than     C16..  coeff.: 1

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings