Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What can cause an HCF [Boards Compatibility] fault on an ATV340 series drive?
Issue:
HCF [boards Compatibility] fault on an ATV340 series drive.

Product Line:
ATV340

Environment:
All

Cause:
The [Pairing password] PPi parameter has been enabled and an option module has been changed.

Resolution:
Refit the original option module.
Confirm the configuration by entering the [Pairing password] PPI if the module was changed
deliberately.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings