Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
When should ATV61/71 internal fan start?
ATV61 and ATV71 drives,
On Size 2 to 5b the fan starts on a temperature threshold THD=70% and is stopped when THD < 60%
On Size 6 to 15 and 690V range the fan starts as soon as the run command is applied.

Size 2 to size 5b are drives from 075N4 till HD18N4 (included).
Size 6 to 15 are drives HD18N4 and above.

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings