Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to interpret if data for cable cross-section is expressed as M6, M8, M10, M12?
Such a data can be found in instruction sheet, as in attachment for instance.

The values expressed as Mxx (e.g. M6,M10, M12) means there is a hole in busbar for connecting the cable with cable lug.
So max cable cross-section then depends on the cable lug you buy.
If you buy cable lug e.g. Cu120 - 12 (see picture) it means that this lug is dedicated for 120mm2 cable and has hole prepared for mounting using M12 bolt.

Schneider Electric UK

Attachment(s)
Cable lug example.jpg [21.57 KB]
Connection.jpg [88.02 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings