ATS22- Why can't I access all programming menus?

Article available in these languages: Czech

Issue:
Can't access more than the Conf, SET, and SUP menus on the ATS22.

Product Line:
Altistart 22

Environment:
All

Cause:
Programming

Resolution:
This is an access level issue. Set LAC= On (Conf menu), and you will have access to all programming menus.