Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Why I cannot discover my Smartlink or PowerTag Link connected to EcoStruxure Power Commission (EPC) ?
For Cybersecurity reasons the Modbus TCP setting might not be enabled by default when receiving the gateway. You need to activate the Modbus TCP feature in the embedded Web Pages of your gateway to make it discoverable by EPC.

Log in to your gateway and go to the SETTINGS meny -> COMMUNICATION -> IP NETWORK SERVICES -> and check that MODBUS TCP checkbox is enabled on port 502.

Try again to discover your Smartlink / PowerTag Link with EPC.

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings