Command with web page is not possible due to Cybersecurity reasons (HTTP requests).
You send a command with the following methods :
You send a command with the following methods :
- EcoStruxure Power Commissioning
- Modbus write requests on Register Adress 0x90BA (Register Number 37051)
Released for: Schneider Electric UK



