What is the minimum overload setting on the Micrologic 2 trip units?

The NSX Micrologic 2 trip unit has adjustable overload protection settings as follows:

Overload setting range: Adjustable between 0.36 and 1 times the rated current (In) of the device.

  • Base adjustment (Io): The front dial allows adjustment between 0.4 and 1 times In. (Io= In x 0.4-1.0)
  • Fine adjustment (Ir): This is a secondary dial that allows fine-tuning of the overload setting, adjustable between 0.9 and 1 times Io. (Ir=Io x 0.9-1.0)