Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to set the dial in Tesys U Motor starters?
Issue:
Do Tesys U Motor starters take into account the service factor?

Product Line:
Contactors and Starters-IEC

Environment:
Tesys U Motor starters

Resolution:
— If the motor has a 1.0 service factor, multiply the motor full-load current by 0.9 and adjust the dial to that number.
— If the motor has a 1.15 to 1.25 service factor, set the adjustment dial to the motor full-load current.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings