Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
SSH script fails to run from PowerChute Network Shutdown with error (java.nio.charset.MalformedInputException: Input length = 1)

Issue:
Configured PowerChute Network Shutdown to run an SSH script, which fails to run and records an error (java.nio.charset.MalformedInputException: Input length = 1).

Product:
PowerChute Network Shutdown version 4.3, 4.4, 4.4.1

Environment:
All support Windows OS

Cause:
The wrong encoding was selected for the script text file.

Solution:
PowerChute Network Shutdown will support text file encoding UTF-8. Save the text file with the required encoding, and PowerChute will trigger it.
SSH Script Encoding

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings