How wired Arc Fault protection in Isobar?

Acti9 Active and Acti9 iARC have to be installed on a DIN Rail.
Therefore an extension enclosure with a DIN rail is required whatever your installation (retrofit or new one).
The extension enclosure can be placed below or a side of main enclosure.
You can refer to the extension enclosures section listed into the Acti9 Isobar P catalogue. (you can refer to page 55 of the catalogue)
In case you intent to use the all in one Acti9 Active product, you should add a terminal block in the Isobar panel board ( as described thereafter).

Needs:
1/ Extension enclosure with DIN rail (ex SEA9BNEX034N or SEA9BN8SXS)
2/ Terminals blocks (SEA9TB1001) to supply phase from Isobar to Acti9 Active product
3/ Acti9 Active device

Fig1:
Fig1 Acti9 Active and Acti9 iARC how to wire


If you intend to use the Acti9 iARC, you must wire it as shown below

Fig2:

Fig2 iARC how to wire

Note: You can also use an AFDD comb busbar to feed AFDDs, which helps reduce wiring work. For more details, please refer to the following FAQ:

How to fit Arc Fault Device (Acti9 Active) on the dinrail enclosure with the AFDD comb Busbar?

Schneider Electric UK

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center