Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
PME2020/PME2021 Use my windows credentials fails with "The user name or Password you entered is invalid"

_____________________________________________________________________________________
Section 1 – Product /System/Environment information

PME2020
PME2021
_____________________________________________________________________________________
Section 2 – Issue

Logging in the WebClient Using my windows credentials fails with "The user name or password you entered is invalid"
_____________________________________________________________________________________
Section 3 – Root Cause

If the Windows Authentication setting is disabled in IIS for the default website, the one-click option won't work.

aa

_____________________________________________________________________________________
Section 5 – Troubleshooting/Proposed Solution
Enable the Windows Authentication setting  in IIS for the default website
Reset IIS and the one-click option will work.

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings