Issue:
Customer has a SAFF code on an ATV630.
Product line:
ATV600 / ATV900.
Environment:
All models, all serial numbers .
Cause:
Drive shows SAFF, needs to clear the fault.
Resolution:
Remove factory jumper from P24, STOA & STOB and reinstall it.

If the code reappears after power cycling, try contacting Drives Technical Support for further troubleshooting.
Customer has a SAFF code on an ATV630.
Product line:
ATV600 / ATV900.
Environment:
All models, all serial numbers .
Cause:
Drive shows SAFF, needs to clear the fault.
Resolution:
Remove factory jumper from P24, STOA & STOB and reinstall it.
If the code reappears after power cycling, try contacting Drives Technical Support for further troubleshooting.
Released for:Schneider Electric UK



