Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Where do I connect the power cables on an ASCO 185 Series Transfer Switch?

Wiring and Installation of the ASCO Series 185 automatic transfer switch (ATS) must be performed by a licensed electrician.

Refer to the ATS wiring diagram.

DANGER! ELECTROCUTION HAZARD: Turn off utility power and turn off the generator to prevent electrocution when wiring the transfer switch.

  • Preferred Source/Utility Source - connect power cables to Terminals L1 & L5 of the ATS
  • Alternate Source/Emergency Source - connect power cables to Terminals L2 & L6 of the ATS
  • Load - connect power cables to Terminals L3 & L7 of the ATS

Wiring 185

185 ATS


You can also download and view the wiring diagram on below link:

ASCO SERIES 185 Power Transfer Switches Product Wiring


If unsure, please contact Technical Support @ 1-800-800-2726 and press 3 or send an email to technicalsupport@ascopower.com

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings