{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Can the ATV212 be used at high elevation?

Issue:

Customer wants to use the ATV212 at elevation over the maximum elevation listed in the Manual (1000 meters).

Product Line:

Altivar 212

Environment:

Altitude over 1000 meters

Cause:

High elevation jobsite

Resolution:

The ATV212 products is limited at 1000m without derating.

You can reach 3000m with current derating 1 % per 100m.

The limit is 2000m for Corner grounded system.

We can not be higher because the rated insulation of the product is designed for altitude up to 3000m.

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: