Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Is it possible replace a PRM without Control Expert?

Yes, it is possible.

In theControl Expert application, under PRM general settings, ensure the following options are checked and properly configured:

  • Create an entry for this device name in the DHCP server
  • Backup the PRM configuration in the FDR server on download

Once these settings are confirmed, follow these steps to correctly replace the PRM:

  1. Remove the PRM module to be replaced.
  2. Prepare the new PRM module:
    • Set its lower rotary switch to ‘E’ (Configuration file deletion) to clear any existing configuration.
    • Power up the new PRM and wait for the boot process to complete, then power it off.
  3. Match the rotary switch positions:
    • Check the rotary switch positions on the old PRM and set the new PRM identically.
  4. Install the new PRM:
    • Power up the new PRM in the same location as the old one.

The new PRM will boot and automatically retrieve its configuration file from the FDR server.

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings