Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Are there any settings needed to run a ATS22 soft start on a Corner Grounded Delta System?

Issue:

Settings needed to run a ATS22 soft start on a Corner Grounded Delta System.

Product Line:

ATS22

Environment:

Corner-Grounded Delta system

Cause:

n/a

Resolution:

When you have a corner grounded system on the ATS22, DO NOT change the DETLA settings in the config menu, leave it as LINE.

Would also suggest to go CONF menu and set LAC to on and then go to the ADJ menu and turn the SSC to off.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings