Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Customer UPS report retrieval for Galaxy VM and Galaxy VX
Issue:
Customer UPS report retrieval for Galaxy VM and Galaxy VX

Product line:
Galaxy VM


Cause:
UPS report needed to troubleshoot UPS alarms properly prior to dispatch

Resolution:
See steps below on how to retrieve UPS report/logs.

The exported log can only be used by Schneider Electric customer support for
analysis.
1. From the home screen on the display select Logs > Export Data
2. Insert a USB device in the USB port located on the front of the display.
Image 1
3. Tap the Start Data Export button.
When the download is complete, the following message will be shown on the
screen: Data Exported Successfully. Remove USB device.
4. Remove the USB device and tap the home button to exit the screen.
5. The exported data on the USB device can now be sent to Schneider Electric
support for analyzing.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings