When using Tesys T, can I use multiple control channels simultaneously?

The Tesys T (LTMR*) motor starter allows you to chose between 3 different control channels (terminal strip, HMI and Network) for each control source (Remote and Local), however, when in operation you can only use Remote OR Local control source at any one time. These control sources cannot be used simultaneously.

When configuring the unit on SoMove, you have to assign the Remote and Local control channels within the parameters list, "control tab", as below:

Local / Remote control channel Selection - Tesys T in SoMove

The options possible for Local and Remote controls are shown in the table below:

Control Channel Options - Tesys T

When in operation, the selection between Local and Remote will be done through input I.6, depending on the wiring mode. This is commonly done by using a Local-Remote selector switch wired to that input.

See user manual for further information: https://download.schneider-electric.com/files?p_Doc_Ref=DOCA0127EN&p_enDocType=User+guide&p_File_Name=DOCA0127EN-03_TeSys_T_Motor_Management_Controller_User_Guide.pdf

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center