Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Do Isobar/Isobar P board require EMC certification?
Isobar/ IsobarP series distribution boards are exempt from requirements for EMC testing due to the nature of the product.
The Isobar/ IsobarP series distribution boards are suitable for category ‘Environment B’ according to BSEN 61439-1:2011– Annex J - Electromagnetic Compatibility (EMC).
The Isobar/ IsobarP series distribution boards do not incorporate any electronic circuits. According to BSEN 61439-1:2011 clause J.9.4.3.2 ASSEMBLIES incorporating electronic circuit
This is also the same for powerpact 4 Boards
Under normal service conditions, ASSEMBLIES not incorporating electronic circuits are not sensitive to electromagnetic disturbances and therefore no immunity tests are required.

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings