Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Resolving 'Missing Module "WonderwareHistorian"' Errors in Recent Geo SCADA Versions

If you observe the error message 'Missing Module "WonderwareHistorian"' upon starting your Geo SCADA server database in newer versions, it signifies that the necessary 'AVEVA Historic Data Export' module is not currently installed or enabled.

WonderWareHistorian

To rectify this issue, shut down the Geo SCADA server, then navigate to your Geo SCADA installation files and initiate a modification of the existing installation. Within the Server tree, locate and enable the 'AVEVA Historic Data Export' feature. Complete the remaining steps of the installation to apply the changes.

AvevaHistoric

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings