What are the Torque settings for NSX MCCB power terminals?

Torque settings for NSX MCCB power terminals are below: 100amp and less rated frames = 10Nm 125-250amp rated frames = 15Nm 400-630amp rated frames = 50Nm These are for the top and bottom power terminals

What does Internal Arc Classification A-F, A-FL and A-FLR mean?

Internal Arc Classification IAC A-F, A-FL and A-FLR are defined in IEC 62217-200 and help to define internal arc performance of medium voltage or high voltage switchgear. The following definitions are described as: A switchgear installation in rooms with access for authorized personnel, closed...

What is the maximum earth loop Impedance Zs value for the circuit breakers used in the Powerpact 4 panel board?

The maximum earth loop Impedance figures can be found on the attached pdf files. 16A to 250A The standard MCCB's used for ratings of 16A to 250A with part numbers beginning with "MGP..." are identical to the NSX with thermal magnetic trip units. 400A & 630A The standard MCCB's used for ratings...

Which is the software to program the Modicon M241?

The software to program the Modicon M241 is EcoStruxure Machine Expert (former SoMachine). In order to install this software you need to download "Schneider Electric Software Installer" from the next link: Schneider Electric Software Installer - setup | Schneider Electric Then you should be able...

Why is the kW (Active Power) showing a negative reading on the Powerlogic series of meter?

A negative kW reading is usually due to one of 2 things The Current transformers (CT's) have been fitted onto the cable or busbar the wrong way round. The P1 side of the CT should be towards the supply and the P2 side of the CT should be towards the load. Alternatively, if the CT is fitted...

EcoStruxure Facility Expert evolution

EcoStruxure Facility Expert TM evolution Schneider Electric is improving and enhancing your experience by transitioning from EcoStruxure Facility Expert to a new solution ecosystem. Here a substitution table comparing legacy Facility Expert subscription type vs. new solution proposed:...

How do I upgrade the firmware on an APC Network Management Card (NMC) or NMC embedded device (Rack PDU, etc)?

Issue You wish to upgrade your Network Management Card's (NMC) firmware or have been instructed to. You have a device such as a Smart-UPS, Smart-UPS Ultra, Easy UPS On-Line, Easy UPS 3-Phase, Rack PDU, AV unit, or environmental monitoring unit with an embedded NMC that you wish to upgrade. You had...

How do I update my Smart-UPS firmware using the web interface of my Network Management Card?

Issue: Because the Firmware Upgrade Wizard is the most universal and preferred method of updating, we recommend using the APC Firmware Upgrade Wizard whenever possible. The APC Firmware Upgrade Wizard guides you through the update process and provides a consistent update experience. The Firmware...

Show more
Popular Video FAQsPopular Videos
Show more
Learn more through our General Knowledge FAQsGeneral Knowledge
What is an Electrical "Ground Loop" - How does it affect my equipment?

Issue: What is an electrical "ground loop" and how does it affect my equipment? Environment: Ground loops can occur in any situation where multiple electrical devices are interconnected, especially when those devices are powered from different sources or located in different places with varying...

How to identify the M172 that I am using in the program?

In order to identify in our code which M172 model we are using we need to use the two (2) internal variables located in "Operators and blocks". The variables are Par_POLI (Polycarbonate code) and sysMSK (Mask number). If a M172 with 28IOs or 42IOs is connected then the variable "sysMSK" is equal to...

What is the difference between in-sync and in-phase?

There is often confusion between the in-phase and the In-sync features of ASCO transfer switches. It is important to understand the difference between these features especially during the process of selecting transfer switches for different applications. In-Phase The in-phase monitor is a feature...

Voltage, Current and Resistance Explained

Issue: How do I remember the relationship of voltage, current and resistance in an electrical system? Environment: N/A Solution: Voltage (unit of measurement - volt) is like the water pressure in the pipe. When you turn on a faucet, the water pressure makes the water flow out. Similarly, voltage...

What are the differences between 380V AC, 400V AC and 415V AC mains supplies and what voltage equipment should I use?

For many years, mainland Western Europe has used a mains 3 phase electricity supply nominally rated at 380V AC 50Hz while the UK used 415V AC 50Hz. Currently, all Western European 3 phase supplies are classified 400V AC. In reality, there is no 400V AC supply unless you create one locally. 400V AC...

What is Power Factor Correction (PFC) - Does it help conserve energy?

Issue: What is Power Factor Correction (PFC) - Does it help conserve energy? Answer: Explanation 1: Power Factor Correction (PFC) doesn't directly reduce the overall electric consumption of a device or system, but it does play a role in optimizing the efficiency of electrical systems, which can...

What size overload do I use with a star delta starter ?

In the majority of cases, the overload of a star delta starter is fitted below the delta contactor with wiring connections to one side of each of the motor windings. The other side of the windings are connected to the line contactor. This means the motor load is split between 2 contactors but the...

Easy-UPS Online Registration

Register the Easy UPS with APC by Schneider Electric customer support. This is a one time process required to be done only during initial installation. The Easy UPS output cannot be turned on without successfully completing registration process. After successful completion of the registration...

Show more
 

Download Centre

Search and download offer documentation, support information, certificates, CAD and software.
 

Download Centre

Search and download offer documentation, support information, certificates, CAD and software.
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.