Issue:
Would an I-line panel with 1200 main breaker have GFI protection as standard per NEC
Product Line:
I-Line Panelboards
Environment:
Products sold in North America
Resolution:
It is required by NEC if panel is 277V, 480V or 480V Delta. It is not required if it is 120-208 volts. In any case the ground fault protection would have to be quoted for factory installation. Check with the local Distributor or Sales office for selection and quotation.
Would an I-line panel with 1200 main breaker have GFI protection as standard per NEC
Product Line:
I-Line Panelboards
Environment:
Products sold in North America
Resolution:
It is required by NEC if panel is 277V, 480V or 480V Delta. It is not required if it is 120-208 volts. In any case the ground fault protection would have to be quoted for factory installation. Check with the local Distributor or Sales office for selection and quotation.
Released for: Schneider Electric USA

