How can we help you today?

Video: How does the neutral get bonded to the enclosure, for service entrance applications, in a high amp (150 A and above) QO or HOMELINE load center?

Article available in these languages:

  • Spanish

Issue:
Installing Neutral Bonding Screw on QO & Homeline Load Centers

Product Line:
QO and Homeline load centers

Environment:
Box Bonding for High Amp, 150A and Above

Cause:
Application

Resolution:
All QO and Homeline load centers that are marked 'Suitable for Use as Service Equipment', will come from the factory with a Green Neutral Bonding Screw, to be installed when the load center is used in a Service Entrance Application.
When a load center is used as Service Equipment, the NEC requires that the neutral shall be bonded to the metal box. The Service Equipment is identified by the fact it includes the first disconnect of the incoming power from the Utility. For a single family house, many times the load center is the main panel, with the main breaker acting as the Service disconnect. In this panel, the green screw is used to bond (fasten) the neutral to the metal box. This is only done in the main panel.
NOTE: Any panels installed downstream of the main panel are called sub-panels, and the neutral in these panels must not be bonded to the box. Since many Load Centers can be used as either the main panel, or as a sub-panel, the green screw is included with the load center to be used in the appropriate installation.
The green screw is also commonly called the "Neutral Bonding Screw", or the "Bonding Screw".

Refer to the Wiring Diagram Label of each load center, the label will be located on the interior sidewall of the enclosure. The Wiring schematic will state "Box bonding when required" and indicate the location on the Main Neutral Assembly of where to install the green bonding screw. The green bonding screw, is a Form Threading(or self-tapping) screw and will require a small amount of force to get the screw started in the hole of the enclosure.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings