What is the Terminal Lug Data for ALL of the 200amp, US and Canada, Heavy Duty Safety Switches (for example; a HU364A, H364, CHU364, CH364, H364DS, H364AWK and CH364AWK)?
Issue:
Product Design Features
Product Line:
Heavy Dutye Safety Switch
Cause:
Terminal lug data
Resolution:
HDSS = Heavy Duty Safety Switches
The 200amp Heavy Duty Safety Switches will accept as standard (1) #6 AWG - 250 kcmil aluminum or copper conductors per phase. The Lug conductor(or wire) temperature rating is 75 degree C.
With the following exceptions:
The H225XJG and H225XJGAA will ONLY use 75 degree Copper wire and accept (1) #3 AWG - 350Kcmil. These are NOT UL listed due to inadequate wire bending space (5" for ON end and 6" for OFF end)
NOTES:
1) There is a Double lug kit available for the 200amp HDSS, BUT it is NOT UL Listed, NOT CSA Listed and is not listed on the switches wiring diagram. It is ONLY for the LOAD side and cannot be used on the LINE Side of the switches. The Lug kit will allow for (2) #6 - 300kcmil AL/CU wires Per Phase and Neutral. The kit part number must be purchased separately for Field installation only. The kit part number is AL20DTF. The Kit contains 3 Lugs
2) The only UL listed alternate lugs are compression lugs, BUT they do NOT change the size or quantity of the standard wires mentioned above.
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.