How can we help you today?

What is the part number for the replacement contacts for LC1FJ contactor?

Issue:
Part number for the replacement contacts for LC1FJ contactor

Product Line:
TeSys F Contactors

Environment:
IEC Contactors and Overload Relays

Resolution:
For three pole devices order LA5FJ431, for four pole devices order LA5FJ441.

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.