Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the tolerance or voltage range for Definite Purpose 8910DPA coils?
Issue:
What is the minimum and maximum control voltage range of  Definite Purpose rated devices?

Product line:
NEMA Contactors and Starters

Environment:
8910 and 8911 Definite Purpose Contactors

Resolution:
Standards state that the coil must operate properly between 85 and 110 percent of the actual rated voltage or range of -15% to +10% of nominal.  Hot drop out voltage is less than 60%.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings