How can we help you today?
How do you check the Series B 8502SG control coil resistance?
Issue:
How to measure 8502 Size 5 Coil resistance?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
Type S Contactors and Starters
Cause:
The coil cannot be measured directly with an ohmmeter
Resolution:
The resistance of this coil cannot be measured with an ohmmeter. A properly functioning coil, when isolated from its control circuit draws between 0.3 ma and 10 ma (depending upon its voltage) when connected to a 9 volt battery
This also applies to all 8536SG, 8538SG, 8539SG, 8606SG, 8630SG, 8640SG, 8702SG, 8736SG, 8738SG, 8739SG, 8810SG, 8903SX, 8910SYD368, and 8940 Size 5 except ``NP`` devices. For enclosed devices, the series information is based on device and not enclosure nameplate
How to measure 8502 Size 5 Coil resistance?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
Type S Contactors and Starters
Cause:
The coil cannot be measured directly with an ohmmeter
Resolution:
The resistance of this coil cannot be measured with an ohmmeter. A properly functioning coil, when isolated from its control circuit draws between 0.3 ma and 10 ma (depending upon its voltage) when connected to a 9 volt battery
This also applies to all 8536SG, 8538SG, 8539SG, 8606SG, 8630SG, 8640SG, 8702SG, 8736SG, 8738SG, 8739SG, 8810SG, 8903SX, 8910SYD368, and 8940 Size 5 except ``NP`` devices. For enclosed devices, the series information is based on device and not enclosure nameplate
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.