What is the part number for a 4000A plug-in tap box for CP2340G bus duct?

Issue:
Part number for a 4000A plug-in tap box for CP2340G bus duct.

Product Line:
Busway

Environment:
Products sold and used in the United States

Resolution:
Plug-in cable tap boxes are available at a rating of 1600A maximum. These can be installed on 4000A plug-in busway. The catalog number for these is either PTB316GH or PTB316GV depending on the mounting orientation of the busway - if the busway is mounted horizontally use the PTB316GH and if the busway is vertical, use the PTB316GV. End cable tap boxes (CF2340GETBMB) are available for use with CP2340G busway.