What is the lug capacity of the QOM2-VH breaker?
Product Line:
QOM2 Circuit Breakers
Environment:
Electrical Distribution Equipment
Resolution:
The lugs will accept #4 - 300 kcmil copper or aluminum when used in a load center, but the wire bending space limits the maximum to 250 kcmil in an enclosure.
QOM2 Circuit Breakers
Environment:
Electrical Distribution Equipment
Resolution:
The lugs will accept #4 - 300 kcmil copper or aluminum when used in a load center, but the wire bending space limits the maximum to 250 kcmil in an enclosure.
Released for: Schneider Electric USA