What is the AIC rating of the bussing provided in all panelboards?
Issue:
Interruping Rating of panels
Product Line:
Panelboards
Environment:
NQ,NF,I-Line,QMB
Cause:
Application
Resolution:
Panelboard bussing does not carry an AIC rating. The overall AIC rating of the equipment is determined by the circuit breakers installed. The overall AIC rating of the panelboard cannot exceed AIC rating of the lowest rated branch breaker unless a series rating can be applied.
Example: Fully rated panel with 65KAIC branches selected for series rating downstream panels. There is also one branch breaker rated 10KAIC. The panel will be rated 10KAIC.
Revised 3/10/04
Interruping Rating of panels
Product Line:
Panelboards
Environment:
NQ,NF,I-Line,QMB
Cause:
Application
Resolution:
Panelboard bussing does not carry an AIC rating. The overall AIC rating of the equipment is determined by the circuit breakers installed. The overall AIC rating of the panelboard cannot exceed AIC rating of the lowest rated branch breaker unless a series rating can be applied.
Example: Fully rated panel with 65KAIC branches selected for series rating downstream panels. There is also one branch breaker rated 10KAIC. The panel will be rated 10KAIC.
Revised 3/10/04
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.