What is the AL1200P25K lug kit data for Powerpact P frame and NS630b - NS1250 breakers?

Product Line:
Circuit Breakers

Resolution:
Conductor:      Al/Cu
Lugs per kit:    3
Construction:  Individually mounted breakers
Conductors:    4
Size:                 3/0 - 500 kcmil
Strip length:     Top holes 1.25 in., Bottom holes 2.25 in.

Torque Values:

Wire binding screw torque:    442.5 lb-in
Lug mounting screw torque: 190 lb-in

Note:

Tool required: Screwdriver, POZIDRIV #2 or #3, or slotted. Socket Wrench, 7mm hex (for wire binding screw). Torque Wrench, 5/16 in. or 8mm.