Issue:
Covert 9422 Type T to a cabled mechanism
Product Line:
Operating Mechanism and Disconnect Switches
Environment:
9422 Disconnect Switches
Resolution:
Non-cable operated mechanisms cannot be converted to cable operated and vice versa.
Available cable mechanisms can ONLY be installed in switches used with cable operators.
Note: This only applies for 30, 60 and 100 amp switches.
Switches compatible with cable operators.
Cable operators to select based on desired cable length.
36 inch cable = 9422CFT30
48 inch cable = 9422CFT40
60 inch cable = 9422CFT50
120 inch cable = 9422CFT10
Covert 9422 Type T to a cabled mechanism
Product Line:
Operating Mechanism and Disconnect Switches
Environment:
9422 Disconnect Switches
Resolution:
Non-cable operated mechanisms cannot be converted to cable operated and vice versa.
Available cable mechanisms can ONLY be installed in switches used with cable operators.
Note: This only applies for 30, 60 and 100 amp switches.
Switches compatible with cable operators.
| Disconnect switch size | Fuse Type | Fuse Clip Rating (A) | Switch used with cable operators | |
| 250V | 600V | |||
| 30 A | None | - | - | 9422TCN30C |
| H, J, K, R | 30 | - | 9422TCF30C | |
| 60 | 30 | 9422TCF33C | ||
| 60 A | None | - | - | 9422TDN60C |
| H, J, K, R | 60 | 30 | 9422TDF60C | |
| - | 60 | 9422TDF63C | ||
| 100 A | None | - | - | 9422TEN10C |
| H, J, K, R | 100 | 100 | 9422TEF10C | |
Cable operators to select based on desired cable length.
36 inch cable = 9422CFT30
48 inch cable = 9422CFT40
60 inch cable = 9422CFT50
120 inch cable = 9422CFT10
Released for: Schneider Electric USA