Issue:
Incoming feed in L-Line panel
Product Line:
Panelboards
Environment:
I-Line Power Distribution Panelboards
Cause:
Mounting flexibility
Resolution:
Yes. I-Line main lug panels can be rotated in the field to accept top or bottom feed.
NOTE: Rotating the interior will affect the location of larger breakers (wide side only) on HCW / HCP, HCWM and HCWM-U / HCR-U. On a bottom feed interior, the "wide side" is on the left of the bus stack. On a top feed interior, the "wide side" is on the right side of the bus stack.