Are NF MLO interiors convertible for bottom feed or top feed?

Issue:
Bottom feed and top feed installation of a NF MLO panelboard.

Product Line:
NF Panelboard

Environment:
Application

Cause:
Clarifying

Resolution:
Yes. This can be accomplished by rotating the interior assembly 180 degrees. Detach the line and load end covers from the branch deadfront, rotate the branch section 180 degrees and re-attach line and load end covers. (This is necessary to achieve proper orientation of deadfront labels.)