How can we help you today?
Is the Transformer data on the Motor Data slide rule for secondary current or primary current?
Issue:
Transformer Amperage chart on the Motor Data Calculator
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
Data on Dry Type Transformer Data chart
Resolution:
The data is applicable to the kVA and voltage and is independent of whether it is the primary or secondary.
For example, an EXN75T3H is a 480 delta to 208Y/120 Transformer. The FLA pn the primary (480V) is 75,000/480/1.732 = 90 amps. The FLA on the secondary (208V) is 75,000/208/1.732 = 208 amps. An EX75T212H is a 208 delta to 480Y/277 transformer. The FLA on the primary (208V) is 208 amps, and the FLA on the secondary (480V) is 90 amps. Note that the FLA is dependent upon voltage and kVA only!
Transformer Amperage chart on the Motor Data Calculator
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
Data on Dry Type Transformer Data chart
Resolution:
The data is applicable to the kVA and voltage and is independent of whether it is the primary or secondary.
For example, an EXN75T3H is a 480 delta to 208Y/120 Transformer. The FLA pn the primary (480V) is 75,000/480/1.732 = 90 amps. The FLA on the secondary (208V) is 75,000/208/1.732 = 208 amps. An EX75T212H is a 208 delta to 480Y/277 transformer. The FLA on the primary (208V) is 208 amps, and the FLA on the secondary (480V) is 90 amps. Note that the FLA is dependent upon voltage and kVA only!
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.