How can we help you today?

Can an adjustable trip circuit breaker be used to protect conductors rated at less than the maximum setting of the circuit breaker?

Issue:
Using an adjustable-trip breaker at less than its maximum setting

Product Line:
Circuit Breakers

Environment:
Powerpact and Masterpact Circuit Breakers with Micrologic Trip Units

Resolution:
A  circuit breaker can be applied at less than its maximum rating if the amp rating is adjusted to a level needed to protect the wire, and if access to the adjusting means is appropriately restricted.
NEC240.6(C) states " ``A circuit breaker that has restricted access to the adjusting means shall be permitted to have an ampere rating(s) that is equal to the adjusted current setting (long-time pickup setting). Restricted access shall be defined as:
(1) Located behind removable and sealable covers over the adjusting means
(2) Located behind bolted equipment enclosure doors
(3) Located behind locked doors accessible only to qualified personnel
(4) Password protected, with password accessible only to qualified personnel
For Micrologic Trip Units, restricted access may be accomplished by installing the MICROTUSEAL Trip Unit Seal onto the cover over the adjusting dials.




Seal illustration

Schneider Electric USA

Attachment(s)
Adjustable Breaker Settings 0613DB0301.pdf [655.28 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings