What is the Terminal Lug Data for ALL of the 800A, US and Canada, Heavy Duty Safety Switches (for example, H367, H367R or H367AWK)?
Issue:
Product Design Features
Product Line:
Heavy Duty Safety Switch
Cause:
Terminal lug data
Resolution:
ALL the 800amp Heavy Duty Safety Switches will accept (3) #3/0 AWG - 750 kcmil aluminum or copper conductors per phase. The Lug conductor(or wire) temperature rating is 75 degree C.
The only alternate lugs are the H8LKE2 compression lug kit, but the compression lugs do NOT allow for any additional or larger wires. See FA120693 for more information on this compression lug kit
More on Safety Switches here.