How can we help you today?
Can an encapsulated wall mount transformer, type A, B or C, be mounted on its side or back?
Issue:
Mounting for encapsulated transformer with type A, B and C enclosure.
Product Line:
Transformers
Environment:
Resin Encapsulated Transformers
Resolution:
It can be mounted on its side or back, however it will no longer be rated Nema 3R. It will then be rated Nema 1. It should not be mounted with the wiring compartment facing upwards. This could result in the wiring compartment temperature exceediing the rating of the insulation system of the conductors contained therein.
Mounting for encapsulated transformer with type A, B and C enclosure.
Product Line:
Transformers
Environment:
Resin Encapsulated Transformers
Resolution:
It can be mounted on its side or back, however it will no longer be rated Nema 3R. It will then be rated Nema 1. It should not be mounted with the wiring compartment facing upwards. This could result in the wiring compartment temperature exceediing the rating of the insulation system of the conductors contained therein.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.