Why can't I select sub feed or thru feed lug options on a main lug only panel with a high AIC rating?
Issue:
Sub-feed or thru feed lug options for a main lug only panel with a high AIC rating

Product Line:
Panelboards

Environment:
Product Selection

Resolution:
The UL 3 cycle rule will not allow you to feed to multiple section panels with high AIC ratings. A possible solution would be to series rate to either a remote or integral main.


Revised 3/10/04