Video: How is the mechanical interlock kit LAD9R1V installed?
Issue:
How do you install the LAD9R1V interlock kit?
Product Line:
TeSys D line contactors and accessories
Environment:
Products sold and used in the United States
Resolution:
The 2 identical TeSys contactors have removable covers on the sides at the top on either side of the contactors. These are removed and discarded. The mechanical interlock component is inserted into the slots of the right and left side contactors which are now close side by side. The supplied control bus is then connected to coils to provide electrical interlocking. Line and load side power connections are also provided.
How do you install the LAD9R1V interlock kit?
Product Line:
TeSys D line contactors and accessories
Environment:
Products sold and used in the United States
Resolution:
The 2 identical TeSys contactors have removable covers on the sides at the top on either side of the contactors. These are removed and discarded. The mechanical interlock component is inserted into the slots of the right and left side contactors which are now close side by side. The supplied control bus is then connected to coils to provide electrical interlocking. Line and load side power connections are also provided.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.